The input current is affected by the supply voltage and impedance.

Typical input current
The values of typical input current are given to aid calculations for power flow and power loss. The values of typical input current are stated for a balanced supply.

Maximum continuous input current
The values of maximum continuous input current are given to aid the selection of cables and fuses. These values are stated for the worst case condition with the unusual combination of stiff supply with bad balance. The value stated for the maximum continuous input current would only be seen in one of the input phases. The current in the other two phases would be significantly lower. The values of maximum input current are stated for a supply with a 2% negative phase-sequence imbalance and rated at the maximum supply fault current.

Model

Typical input current A

Maximum continuous input current A

Cable Size UL 508C

Cable size EN60204
Fuse rating   Input AWG Output AWG 

Fuse rating IEC gG A

Input mm2

Output mm2

SP1201

7.1

9.5

10

14
18

10

1.5

1

SP1202

9.2

11.3

15
14
16

12

1.5

1

SP1203

12.5

16.4

20
12
14

20

4

1

SP1204

15.4

19.1

20
12
14

20

4

1.5

SP2201

13.4

18.1

20
12
14

20

4

2.5

SP2202

18.2

22.6

25
10
10

25

4

4

SP2203

24.2

28.3

30
8
8

32

6

6

SP3201

35.4

43.1

45
6
6

50

16

16

SP3202

46.8

54.3

60
4
4

63

25

25

SP1401

4.1

4.8

6
18
22

6

1

1

SP1402

5.1

5.8

6
16
20

6

1

1

SP1403

6.8

7.4

10
16
18

8

1

1

SP1404

9.3

10.6

15
14
16

12

1.5

1

SP1405

10

11

15
14
14

12

1.5

1

SP1406

12.6

13.4

15
14
14

16

2.5

1.5

SP2401

15.7

17

20
12
14

20

4

2.5

SP2402

20.2

21.4

25
10
10

25

4

4

SP2403

26.6

27.6

30
8
8

32

6

6

SP3401

34.2

36.2

40
6
6

40

10

10

SP3402

40.2

42.7

45
6
6

50

16

16

SP3403

51.3

53.5

60
4
4

63

25

25

SP3501

5

6.7

10
16
18

8

1

1

SP3502

6

8.2

10
16
16

10

1

1

SP3503

7.8

11.1

15
14
14

12

1.5

1

SP3504

9.9

14.4

15
14
14

16

2.5

1.5

SP3505

13.8

18.1

20
12
14

20

4

2.5

SP3506

18.2

22.2

25
10
10

25

4

4

SP3507

22.2

26

30
8
8

32

6

6

* Use Fuse class RK1 or similar HRC fuse.