UL Listing Information

The Control Techniques UL file number is E171230. Confirmation of UL listing can be found on the UL website: www.ul.com.

Conformity

The drive conforms to UL listing requirements only when the following are observed:

" The drive is installed in a type 1 enclosure, or better, as defined by UL50
" Class 1 60/75°C (140/167°F) copper wire only is used in the installation
" The ambient temperature does not exceed 40°C (104°F) when the drive is operating
" If the drive control stage is supplied by an external power supply (+24V), the external power supply must be a UL Class 2 power supply

Motor Overload Protection
The drive provides motor overload protection. The overload protection level is 150% of full-load current (FLC) of the drive in open loop mode and 175% of full-load current (FLC) of the drive in closed loop vector or servo modes. It is necessary for the motor rated current to be entered into Pr 0.46 (or Pr 5.07) for the protection to operate correctly. The protection level may be adjusted below 150% if required. Refer to section 8.3 Current limits on page 84 for more information. The drive also provides motor thermal protection. Refer to section 8.4 Motor thermal protection on page 84.

Overspeed Protection
The drive provides overspeed protection. However, it does not provide the level of protection afforded by an independent high integrity overspeed protection device.

Power dependant UL information
Unidrive SP conforms to UL listing requirements only when the following is observed:

" The correct UL-listed class CC fast acting fuses, e.g. Bussman, Limitron KTK series, Gould Amp-Trap ATM series or equivalent, are used in the AC supply.